Please use this identifier to cite or link to this item:
https://dspace.ncfu.ru/handle/20.500.12258/24248| Title: | On the Calculation of Distribution Network Parameters by Automated Metering Systems when Connecting Single-Phase Subscribers to Different Sections of the Neutral Wire |
| Authors: | Danilov, M. I. Данилов, М. И. Romanenko, I. G. Романенко, И. Г. |
| Keywords: | Complex resistances of wires;Distribution networks;Identification method;Line diagnostics;Network parameters;Three-phase four-wire circuit |
| Issue Date: | 2023 |
| Citation: | Danilov, M.I., Romanenko, I.G. On the Calculation of Distribution Network Parameters by Automated Metering Systems when Connecting Single-Phase Subscribers to Different Sections of the Neutral Wire // Proceedings - 2023 International Conference on Industrial Engineering, Applications and Manufacturing, ICIEAM 2023. - 2023. - pp. 7-12. - DOI: 10.1109/ICIEAM57311.2023.10139189 |
| Series/Report no.: | Proceedings - 2023 International Conference on Industrial Engineering, Applications and Manufacturing, ICIEAM 2023 |
| Abstract: | The paper deals with the issue of calculating of the wires complex resistances of a four-wire low-voltage (0.4 kV) distribution network according to the data of an automated energy consumption metering system, provided that single-phase subscribers are connected to different sections of the neutral wire and the resistances of the phase and neutral wires are equal. An algorithm (method) for solving this problem is proposed and calculation expressions using data on voltages, active and reactive powers at subscribers and in the power node, which correspond to the same time periods of two different network operation modes are obtained. The proposed calculation equations are verified with computational experiments on the mathematical model of the distribution network. The results obtained can be useful in the implementation of the functions of the network electrical losses monitoring and diagnosing of the technical condition of the phase and neutral wires of the main line sections in automated metering systems. |
| URI: | http://hdl.handle.net/20.500.12258/24248 |
| Appears in Collections: | Статьи, проиндексированные в SCOPUS, WOS |
Files in This Item:
| File | Size | Format | |
|---|---|---|---|
| scopusresults 2663 .pdf Restricted Access | 131.26 kB | Adobe PDF | View/Open |